|
Heating, Ventilating, and Air-Conditioning (HVAC)
Natural Ventilation
Outdoor air is required for ventilation
purposes, but can also be used to remove internal heat loads. When
the outdoor air is cool (14-23°C) it can be used to cool the occupants.
Increased air movement also has a cooling effect on occupants. This
strategy should be used in conjunction with an adaptive comfort
model.
Natural ventilation can be successfully
utilised as a form of free air-conditioning when the external
temperatures
are appropriate, however, external noise control can be a significant
issue that needs to be considered. Some locations (eg adjacent
to
particularly busy roads/freeways) could preclude the use of natural
ventilation. It is very important that these issues are considered
early and appropriate noise mitigation incorporated into the design.
For office spaces it will not be
possible to achieve appropriate indoor adaptive comfort conditions
for the entire year, however, this system may be used effectively
in conjunction with a mixed mode air conditioning strategy and
thermal
mass. Prior to considering natural ventilation strategies consider
the following issues:
- Air quality suitable for natural ventilation
- Noise environment of site
- Stringent internal cleaning requirements
- Stringent internal air movement and conditioning
requirements
Several strategies exist to make
use of natural ventilation.
In Canberra, Australia, Arup have
designed a building with a temperatures range from 19°C in winter
up to 26°C in summer with no control of humidity. This naturally
ventilated building has been well received by the occupants, who
have expressed feeling healthier due to the improved indoor air
quality.
Air-Conditioning
Design Conditions
Based on guides set out by the Australian
Institute of Refrigeration, Air-Conditioning and Heating (AIRAH),
the base building mechanical services should comply with the following
as a minimum:
External Design Conditions:
| - |
Sydney |
Wagga
Wagga |
Newcastle |
Lismore |
Wollongong |
| Summer |
32°C
DB |
39°C
DB |
32°C
DB |
35°C
DB |
32°C
DB |
| - |
24°C
WB |
22°C
WB |
23.5°C
WB |
24°C
WB |
23°C
WB |
| Winter |
7°C
DB |
1.5°C
DB |
4.5°C
DB |
9.0°C
DB |
7°C
DB |
For further information on locations
within NSW please refer to the AIRAH guideline.
Internal Design Conditions:
Air-conditioning systems should
generally be designed to provide 22.5°C ± 1°C.
Calculated heat gains should include
all simultaneous solar, infiltration, casual, lighting and machine
loads. The following internal loads may be considered a typical
minimal allowance:
For a PCA Premium Grade Building:
| People |
General
Office |
1/10m² |
| |
Meeting
Spaces |
Variable,
approx 1/3m² |
| Machines |
General
Areas |
25w/m² |
| Lighting |
General
Areas |
15w/m² |
For a PCA Grade A building:
| People |
General
Office |
1/10m² |
| - |
Meeting
Spaces |
Variable,
approx 1/3m² |
| Machines |
General
Areas |
15w/m² |
| Lighting |
General
Areas |
15w/m² |
Calculated heat losses should include
thermal and infiltration loads only with no allowance for any internal
heat gains.
Systems
The air-conditioning running and
operating costs contribute significantly to the energy demands on
the building. Choosing the right air-conditioning system can significantly
reduce the energy output from the building. The following should
be considered when reviewing an air conditioning system:
- Arrangements are in place
for after hours use of air-conditioning.
- System is zoned appropriately to deal
with aspect of building, differences in operational demands etc.
Temperature sensors are located to
avoid direct solar gain, heat transfer through external walls etc.
Systems should generally comply with the requirements of the Building
Code of Australia, Volume One – Part F4.
Standard industry air-conditioning
systems include (a combination of systems is also often commonly
found):
- Variable Air Volume System (VAV)
- Constant Air Volume System (CAV)
- Displacement System
- Chilled Beams or Ceilings
Variable Air Volume (VAV)
A VAV system as the
title suggests varies the amount of air supplied to the building
depending on the cooling requirements. The building should be
zoned
to a minimum of north, south, east and west perimeters as well
as an internal zone. The VAV system will provide cooling to these
zones
based on the cooling requirements within them. For example, early
morning, the east zone will require more cooling than the west
zone,
therefore the amount of air supplied to the west zone will be reduced.
A re-heat coil for the individual zones is used to control the
temperature
within them. All fans and pumps will have a variable speed drive
so as to vary their duty depending on the requirements. The ability
to reduce the duties result in reduced running costs.
Constant Air Volume Systems (CAV)
A CAV system as the
title suggests supplies a constant volume of air to the space,
varying temperature depending on the cooling requirements. As
with VAV,
a CAV system should be zoned to a minimum of north, south, east
and west perimeters as well as an internal zone using a form of
re-heat
by either electric or hot water coils as described above. This
system is not as energy efficient as a VAV installation as fans
and pumps
will operate at full design duty at all times i.e. no variable
speed devices enabling a reduction in duties and therefore running
costs
will typically be installed.
Displacement Systems
Displacement systems supply air at
a low velocity, generally 0.2m/s at low level into an occupied space.
The cooler air supply forms a boundary layer at low level, which
slowly rises replacing the air present in the room. At the heat
sources, people and equipment, the air ascends and is removed at
high level. The heat loads and pollutants are removed from the room
rather than mixed as in traditional systems. The supply air temperature
should be 1-3°C less than room temperature. A displacement system
for a room 2.8-3m can typically remove a specific cooling load of
40W/m2. The displacement system conditions only the occupied space
rather than mixing the whole occupied volume. This results in a
smaller chiller size, which reduces running cost and plant space
requirements. The fan power is reduced because of the low pressures,
due to the low velocities.
Chilled Beams/Ceiling
Chilled water is run through tubes
laid in the ceiling or factory assembled beams to carry off the
room-cooling load. The cooling capacity is transferred to the indoor
air through radiation with the remaining through convection. The
radiation and convection shares depend on the design of the chilled
ceiling system. For example a chilled ceiling which is integrated
into a closed room ceiling contributes over 50% of the cooling directly
to the body through radaitive exchange rather than cooling the air
which then cools the body. Due to the ceiling removing a large proportion
of the cooling load, the air volume supplied to the room can be
reduced. (Air is still supplied to meet fresh air requirements and
to remove to latent load). A typical chilled ceiling can achieve
a specific cooling capacity of 60-90 W/m2. The reduction in air
volume results in low noise levels, reduction in plant space requirements,
lower energy costs and lower maintenance costs.
A chilled ceiling system should
be used in conjunction with a displacement system when cooling
loads
are too high for the displacement system alone. Reducing the flow
rate through the ceiling can reduce the capacity of the cooling
load. Therefore, the pumps should be variable speed drive and the
pipework zoned to a minimum of north, south, east and west perimeter
and internal zones.
Hybrid Ventilation
The capability to avail of natural
ventilation in the office area when external conditions are favourable
should be investigated and costed on analysing the air-conditioning
above options. The air-conditioning zones should be arranged so
as the system shuts down or is automatically altered to operate
in 'free cooling' mode (see above) on an occupant opening a window
in that respective zone. Operable windows linked to the BMCS (Building
Mangement Control System) with an open free area exceeding 5% of
the total serving floor area should be allowed in the façade. A
remote link to the BMCS indicating when external conditions favour
natural ventilation should also be installed in each zone.
Zoning
Final air conditioning zones will
be dependant on the chosen system but should at minimum be sectioned
to independently control (water coil re-heat) a north, south, east
and west perimeter (4m depth off façade) as well as an internal
zone.
Hybrid areas will require many sub-zones
interlocked with operable windows to operate efficiently.
Mechanical Ventilation
Filtered outside air is mechanically
supplied and extracted through a network of ductwork and air grilles.
Room air is extracted and ducted to roof level exhaust plant for
discharge to atmosphere. A negative pressure is maintained in these
areas to prevent the migration of odours to the adjacent areas.
Ventilation systems should
be designed in accordance with the requirements of Australian
Standard
AS 1668.2.
Where heated mechanical ventilation
is required the outside air supplied to the space should be
heated
to maintain a set-point temperature within the space. Heating is
to be by way of Low Temperature Hot Water (LTHW) heating coils
served
by the gas boiler (see section to follow).
Mechanical Exhaust
Plant or amenity exhaust air is
extracted and ducted to roof level exhaust plant for discharge
to atmosphere.
A negative pressure is maintained in rooms served in order to prevent
the migration of odours to the adjacent areas. Passive make-up
air
may be by way of door grilles or ceiling mounted transfer duct
and grilles.
Ventilation systems should be designed
in accordance with the requirements of Australian Standard AS
1668.2.
Heating
LTHW
generated centrally by heat pump or gas fired boiler located in
a purpose built boiler plantroom should be used for primary space
heating as a minimum and although electric re-heat is common, LTHW
re-heat coils are more energy efficient.
LTHW is distributed through copper
pipework to various heating coils serving the air-conditioned and
treated ventilation spaces.
THW panel convectors may be used
for underfloor heating or similar.
The use of reverse cycle air-conditioning
may be used where appropriate.
|