|
Electrical Power Systems
Power Distribution
The design of the incoming power
supply is critical for future expansion capacity and reliability
of supply. The main criteria to establish early are the following:
- Capacity of supply;
- Location of the main power distribution
centre; and
- The required level of reliability and
future flexibility of the incoming supply.
The capacity for the site is usually
determined at concept stage on a watts/m2 basis, which is calculated
depending on usage, i.e. commercial, retail, educational, etc.
and diversity between usage types.
The major cost of the electrical
installation can be attributed to the cost of distributing the energy.
It is therefore preferable to locate the main distribution centre
centrally to the main electrical loads, which in addition to the
built area would also include mechanical plant rooms, lifts and
water heating installations. The distribution generally originates
at the low voltage Main Switchboard. Submains cables then feed Distribution
Switchboards which are located locally to the electrical loads.
These would typically be one per floor or building wing. From the
Distribution Switchboards final subcircuits feed individual outlets
or equipment. Typically the subcircuits will feed outlets or loads
within approximately a 100m radius. If longer lengths are required
then additional Distribution Switchboards should be considered.
If the electrical installation requires
an incoming supply in excess of 250kW a high voltage supply should
be considered. The economics of whether a low voltage or high voltage
supply is more efficient will depend on the actual location and
access to a suitable Supply Authority network. If a high voltage
supply is required then a transformer substation will be required.
Typically transformer substations come in two general types as
follows:
- Indoor substation, which
is where the high voltage switchgear and transformers are located
within the building. Supply Authority regulations stipulate minimum
size and access requirements.
- External kiosk type, which is where
the high voltage switchgear and transformer are housed in a
weatherproof
enclosure. Supply Authority regulations stipulate minimum size,
clearance from the building and access requirements.
Power distribution over a long distance is more
effective at high voltage rather than low voltage. Therefore,
if
a high voltage supply is required due to the capacity then the
substation should be located as close as possible to the low voltage
Main Switchboard.
Since the usage of the building sometimes changes
over the building life and the relatively high cost for the incoming
supply it is reasonable to allow spare capacity for future expansion.
It would be reasonable to provide an additional 20% for future expansion
for normal applications. Special applications need to be determined
based on the current use and the envisaged future use.
As a rule of thumb, this additional component
should only be utilised with a change of building use.
Special applications may also require higher levels
of supply reliability then the standard single incoming supply.
This would usually apply to critical business, process or health
facilities. In these cases special supply arrangements need to be
designed as part of the concept design.
Power Distribution Space Requirements
The following spaces should be provided for the
standard electrical installations:
- Incoming Supply Authority
fuses and metering. This will vary from a simple space on an external
wall not subject to mechanical damage to a separate room/s for
larger buildings depending on application. The fuses and metering
need to be accessible by the Supply Authority during normal business
hours.
- Room for the Main Switchboard which can
be combined with the supply Authority Fuses and Metering if required.
These would usually be ventilated rooms with easy access for maintenance.
The Australian Standard AS 3000 has specific requirements for
access, space and signage.
- For larger installations electrical risers
are required to accommodate the submains cabling running up through
the building.
- For larger installations wall enclosures
or small rooms will be required for the Distribution Switchboards.
Internal Lighting
The lighting design should be developed in a manner
which addresses the following attributes:
Lighting level defined as illuminance measured
in Lux. Minimum standards defined by AS 1680 and the Building
Code
of Australia:
- Consideration of the impact
of glare, recommended standards defined by Australian Standards;
- Consideration of any colour requirements
for the lighting;
- Aesthetics of the space and the influence
of the lighting as part of this;
- Flexibility to accommodate typical use
of the space, i.e. open plan or modular office;
- Means of lighting control;
- Lamp types and the expected lamp life;
and
- Energy efficiency, which is defined as
efficacy.
The best lighting design solution seeks to resolve
all of the above points. However, in practice often different aspects
need to be traded off and the lighting design will recognise which
aspects are most important and which aspects are more nominal.
For general commercial applications it is crucial
to meet the minimum defined illumination levels and prescribed glare
criteria. The design calculations for these should include a realist
maintenance factor which allows for degraded light output due to
dust build up, lamp survival factor, etc. and based on average light
output taking into consideration the reduced light output after
a defined period of operation.
Emergency Evacuation Lighting and Exit Signage
Emergency lighting and illuminated
exit signage is generally required to provide occupants with a
safely
illuminated escape route from a building in the case of emergency
and particularly when mains power may not be available. The need
for emergency and exit lighting is defined in the Building Code
of Australia (BCA). The mandatory requirements for this system,
if required,
are defined in the AS 2293.
In general, there are several kinds
of emergency lighting system, which meets the BCA and Australian
Standard requirements:
- Maintained, i.e. the emergency
lamp/s of the fitting is continuously illuminated; and
- Non-maintained, i.e. the emergency lamp/s
of the fitting is not illuminated when normal supply is available.
The emergency and exit luminaries
can be supplied via either one of two systems:
- Central battery system,
where the emergency batteries, battery charger, inverter and controls
are located centrally and a cable distribution network connects
each of the emergency and/or exit signs together; and
- Self-contained system, where each emergency
exit light or exit sign has it’s own battery, battery charger,
inverter and controls integral with the light fitting or mounted
very close to it.
If the number of self-contained
luminaires is larger and regular maintenance difficult then all
the luminaries can be monitored by a centralised computer system.
This simplifies the regular statutory testing required and general
maintenance of the system. However, it is usually only required
on very large installations.
|