|
Fire Services
Buildings Over 25 Metres High (High
Rise Offices)
Objective
The objectives of the provisions
of the Building Code of Australia (BCA) for fire fighting equipment
and services are to:
- safeguard occupants from
illness or injury while evacuating during a fire;
- provide facilities for occupants and
the fire brigade to undertake fire-fighting operations; and
- to prevent the spread of fire between
buildings.
The fire fighting equipment and services
are being provided to meet the minimum deemed-to-satisfy provisions
for this proposed building.
The functional statement and performance
requirements of the BCA would be complied with if the following
fire fighting services are provided.
Fire Hydrants
The fire hydrant service shall
be installed to satisfy clause E 1.3 of the BCA, AS 2419, AS 3500
and the local fire brigade requirements.
The fire hydrants shall be
located in fire stairs throughout the building to provide effective
coverage for fire fighting operations to the local fire brigade
requirements.
The fire hydrant system shall
be provided with fire brigade booster facilities and be located
in an approved location to facilitate the intervention by emergency
services.
Fire Hose Reels
A fire hose reel service shall
be installed to satisfy clause E 1.4 of the BCA, AS 2441, AS 3500
and local government requirements.
Fire hose reels shall be located
adjacent to fire stairs to provide effective coverage for fire fighting
operations.
Automatic Sprinkler System
The automatic sprinkler system
shall be installed to satisfy clause E1.5 of the BCA, AS 2118.1
and local government requirements.
The sprinkler system will be
designed to light hazard and or ordinary hazard OH1 and OH2 for
the office areas and car park areas.
Automatic Fire Detection and
Alarm System
An automatic fire detection and alarm
system shall be provided to satisfy Specification E 2.2a of the
BCA, AS 1670.1 and the local government requirements.
The automatic smoke detection and
alarm system shall protect the whole of the building and associated
facilities for smoke hazard management control.
The automatic fire and smoke detection
system will have a main fire indication panel, microprocessor type
capable of operating a distributed and or multi loop network of
conventional and or analogue addressable smoke and heat detectors
and other ancillary devices, i.e. zoned smoke hazard management
controls conforming to the BCA 1996 and AS 1668-1 for a stair pressurisation
system.
The heat detectors will be provided
in areas not suitable for smoke detectors.
The smoke hazard management system
will interface with essential services equipment via the main FIP
fire fan control module.
Smoke detection will be provided
outside each fire stair in all areas and shall interface with any
required stair pressurisation system(s).
Portable Fire Extinguishers
Portable fire extinguishers shall
be provided to satisfy clause E 1.6 of the BCA, AS 2444 and local
government requirements.
Generally fire extinguishers shall
be distributed throughout the building in areas of specific hazard
and shall be chemical type fire extinguishers.
Fire extinguishers in public areas
shall be located in clear cover security cabinets to minimise the
potential risk of vandalism.
Emergency Warning and Intercommunication
System (EWIS)
A building occupant warning system
(EWIS) shall be provided to satisfy clause E 4.9 for a Class 5 office
type building required to comply with the BCA, AS 2220 and local
government requirements.
EWIS shall be interfaced with other
essential services, i.e. automatic fire detection and alarm systems
and smoke hazard management controls including provision of a remote
PA system console in a designated security and/or reception area.
EWIS speakers shall be provided throughout
all areas of the building as surface mounted 100 dia speakers fittings
with horn speakers in the basement car park areas.
Distribution Piping and Wiring
Systems
The fire services and life safety
distribution piping and wiring systems shall be coordinated with
the architectural design and all other services to follow set services
routes throughout the complex to conceal services wherever possible
and minimise any access for maintenance and servicing.
Passive Fire Protection
All fire services passing through
any walls, floors and ceilings required to have a Fire Resistance
Level (FRL) rating will be sealed with approved passive fire protection
systems to satisfy Section C, Part C3 of the BCA, AS 1530 and local
government requirements.
Fire Safety Management
A comprehensive set of fire safety
management and evacuation plans should be developed which are consistent
with all fire protection equipment to be installed and EPA regulations
relating to OH&S and fire safety. AS 3745 should be used as a guide.
Buildings Under 25 Metres High (Low
Rise Offices)
Objective
The objectives of the provisions
of the BCA for fire fighting equipment and services are to:
- safeguard occupants from
illness or injury while evacuating during a fire;
- provide facilities for occupants and
the fire brigade to undertake fire-fighting operations; and
- prevent the spread of fire between buildings.
The fire fighting equipment and services
are being provided to meet the minimum deemed-to-satisfy provisions
for this proposed building.
The functional statement and performance
requirements of the BCA would be complied with if the following
fire fighting services are provided.
Fire Hydrants
The fire hydrant service shall be
installed to satisfy clause E 1.3 of the BCA, AS 2419, AS 3500 and
the local fire brigade requirements.
The fire hydrants shall be located
in fire stairs throughout the building to provide effective coverage
for fire fighting operations to the local fire brigade requirements.
The fire hydrant system shall be
provided with fire brigade booster facilities and be located in
an approved location to facilitate the intervention by emergency
services.
Fire Hose Reels
A fire hose reel service shall be
installed to satisfy clause E 1.4 of the Building Code of Australia,
AS 2441, AS 3500 and local government requirements.
Fire hose reels shall be located
adjacent to fire stairs to provide effective coverage for fire fighting
operations.
Automatic Sprinkler System
The automatic sprinkler systems are
not required for buildings under 25 metres high to satisfy clause
E1.5 of the BCA, AS 2118.1 and local government requirements unless
they exceed the area volume limitations as a large isolated building
and or exceed the fire compartmentation requirements as a deemed
to satisfy building under the BCA.
Automatic Fire Detection and
Alarm System
An automatic fire detection and alarm
system shall be provided to satisfy Specification E 2.2a of the
BCA, AS 1670.1 and the local government requirements.
The automatic smoke detection and
alarm system shall protect the whole of the building and associated
facilities for smoke hazard management control.
The automatic fire and smoke detection
system will have a main FIP, microprocessor type capable of operating
a distributed and or multi loop network of conventional and or analogue
addressable smoke and heat detectors and other ancillary devices,
i.e. zoned smoke hazard management controls conforming to the BCA
1996 and AS 1668-1 for underground carpark exhaust system.
The heat detectors will be provided
in areas not suitable for smoke detectors.
The smoke hazard management system
will interface with essential services equipment via the main FIP
fire fan control module if required by the BCA.
Smoke detection will be provided
in each fire stair and in all areas of the building including all
concealed ceilings, roof spaces and air handling systems for i.e.
supply and return air smoke monitoring as required by the BCA for
the building classification.
Portable Fire Extinguishers
Portable fire extinguishers shall
be provided to satisfy clause E 1.6 of the BCA, AS 2444 and local
government requirements.
Generally fire extinguishers shall
be distributed throughout the building in areas of specific hazard
and shall be chemical type fire extinguishers.
Fire extinguishers in public areas
shall be located in clear cover security cabinets to minimise the
potential risk of vandalism.
Emergency Warning and Intercommunication
System (EWIS)
A building occupant warning system
(EWIS) shall be provided to satisfy clause E 4.9 for a Class 5 office
type building required to comply with the Building Code of Australia,
AS 2220 and local government requirements.
The EWIS system shall be interfaced
with other essential services, i.e. automatic fire detection and
alarm systems for smoke hazard management controls including provision
of a remote PA system console in a designated security and/or reception
area.
EWIS speakers shall be provided throughout
all areas of the building as surface mounted 100 dia speakers fittings
with horn speakers in the basement carpark and plant room areas.
Distribution Piping and Wiring
Systems
The fire services and life safety
distribution piping and wiring systems shall be coordinated with
the architectural design and all other services to follow set services
routes throughout the complex to conceal services wherever possible
and minimise any access for maintenance and servicing.
Passive Fire Protection
All fire services passing through
any walls, floors and ceilings required to have a fire resistance
level (FRL) rating will be sealed with approved passive fire protection
systems to satisfy Section C, Part C3 of the BCA, AS 1530 and local
government requirements.
Fire Safety Management
A comprehensive set of fire safety
management and evacuation plans should be developed which are consistent
with all fire protection equipment to be installed and EPA regulations
relating to OH&S and fire safety. AS 3745 should be used as a guide.
|